90 EZware5000 Series Programming Manual
1010-1007, Rev. 10
3. Options: The Startup window no. selects the window number that will be displayed every time the HMI is
started up. Window 10 is the default startup window.
The Common window determines if objects in the common window (window 4) are placed above or below
the base window.
The Object layout drop-down determines the layout and display of objects by selecting either Control mode
or Nature mode.
Normally, an object that is controlled by a PLC Register (i.e., a Word Lamp, Bit Lamp, Animation, etc.) is
brought to the Top Layer when the value in the PLC Register changes. This behavior can be changed by the
Object layout option. A setting of Control sets the behavior as outlined above. A setting of Nature (default
setting) will result in the object remaining at the layer assigned during development.
The Keyboard caret color drop-down allows you to set the color of the cursor.
The RW_A enabled checkbox enables an extra 64K of recipe storage memory.
4. Event: When the Use LW9450-9455 as time tags of event logs box is checked, the Time/Date stamp for
items in the Event Display will be taken from Local Words LW9450-9455. You can select the data format of
the Time/Date stamp BCD (binary-coded decimal) or BIN (16-bit signed decimal).
If unchecked, the Time/Date stamp is taken from the selected clock (HMI RTC or External).
Extra No of events: N/A
5. Keyboard: Lists the windows that have been configured as keyboards.
Add: Opens a window list from which you can select an additional window to be available as a project
keyboard.
Delete: Deletes the selected keyboard from the list.
6. Project protection (i series only): When checked, the HMI will compare the value in the Project key field to
the 32-bit unsigned value stored in HMI Local Words LW9046 and LW9047. If the value is different, the HMI
will not run the project.
i series includes the HMI5043N, HMI5043T, HMI5056N, HMI5070NH, HMI5070TH, HMI5100N, HMI5100T,
and HMI5104TH.