92 EZware5000 Series Programming Manual
1010-1007, Rev. 10
6. Disable buzzer: When checked, the HMI will not sound the buzzer (beep) when the screen is touched. Local
Bit LB9019 can be used to control the buzzer. Set the bit to disable the buzzer and clear the bit to enable the
buzzer.
7. Prohibit remote HMI connecting this machine: When checked, the HMI will not allow connections from a
remote HMI. Local Bit LB9044 can be used to control remote connections. Set the bit to disallow remote
connections, clear the bit to allow remote connections.
This setting controls whether or not other HMIs can connect to this HMI. It does not affect how this HMI
connects to other HMIs.
8. Disable upload function (effective after rebooting HMI): When checked, prevents the project from being
uploaded from the HMI (sets LB9033 ON). Reports “error: uploading /mt8000/001/mt8000.”
9. Prohibit password remote-read operation: When checked, a remote HMI cannot read from the local words
containing the Project and User password data (sets LB9053 ON).
10. Prohibit password remote-write operation: When checked, a remote HMI cannot write to the local words
containing the Project and User password data (sets LB9054 ON).
11. Use a disconnection icon on relative objects when PLC communication fails: When checked, any object that
cannot be resolved due to communication loss will be displayed with a special icon:
12. VNC server: Check Password from project to use the password entered in the Password box for a VNC client
to use to connect to the HMI’s internal VNC server (applies to Ethernet-equipped models only). When not
checked, use the VNC password entered in the HMI’s System Settings VNC Server Setting tab.
The VNC Server Password is stored in Local Words LW9530-9537.
13. LW protection: When checked, remote HMI(s) are prevented from writing to the range of Local Word
addresses specified in the LW range boxes.
14. RW protection: When checked, remote HMI(s) are prevented from writing to the range of Recipe Word
addresses specified in the RW range boxes.
15. EasyAccess server: Check Login EasyAccess server to enable EasyAccess in the HMI. See Technical Note
5082, “Using EasyAccess” for more information.